| Specifications |
| Input Voltage |
: |
-48V DC (230V, 50Hz AC option also available) |
| Operating Voltage |
: |
-12V DC (Battery backup available as option for mains operated model only) |
| LED Indications |
: |
POWER ON
ON BATTERY FIRE FAULT SECURITY FAULT ZONE OPEN |
| Controls |
: |
2 Position Key Switches
One key switch for FAULT acknowledgement One push button switch for zone reset |
| Ambient Temperature |
: |
0 - 50°C |
| No. of Zones |
: |
Four (Selectable as Smoke/Fire, Security) |
| Sensors / Zone |
: |
Upto Eight |
| Intrusion Timeout |
: |
30 sec |
Current Ratings for Zones Fire Zone Normal Alarm Security Zone Normal Alarm |
: |
5mA 100mA (max)
5mA 100mA (max) |
| Hooter |
: |
Current 0.5A max.
(Number of hooters limited to maximum current drawn of 0.5A.) |
| Battery |
: |
12V, 4.2AH, (12V, 7AH Option also available) |
| Remote indication |
: |
Independent potential free contacts for fire and security zone. |
| Physical Dimensions |
: |
235(L) X 165(H) X 93(D) mm3 |